6 Configuration
6.1 Digital inputs/outputs
The digital input/output module has 12 channels, each of which can be configured as digital
input or digital output.
The digital outputs are actuated by assigned external inputs (NV_DO01 to NV_DO12).
Assigned external inputs (NV_SR01 to NV_SR12) are also used to suppress the signals of the
digital inputs.
Chapter 6.2 "NV connecting list", page 36
Setup dialog
Parameters
NOTE!
The parameters described in this section can be configured either with the setup program or
with the multifunction panel.
Parameters Selection/settings Description
Function Input The relevant channel is configured as
input.
Output The relevant channel is configured as
output.
Inverting Inverting of the input signal or the output signal (depending on the configuration of
the channel)
Normal Not inverted
Inverse Inverted
Level at suppres-
sion
Input signal level during active signal suppression
Inactive Low level (0)
Active High level (1)
TAG number 7 characters Identification marking (documentation in