JUMO mTRON T
Measuring, Control, and Automation System
Analog Input Module 4-Channel
B 705020.0
Operating Manual
2013-06-18/00575607
Vedere la pagina 0
1 2 3 4 5 6 ... 69 70

Sommario

Pagina 1 - JUMO mTRON T

JUMO mTRON TMeasuring, Control, and Automation SystemAnalog Input Module 4-ChannelB 705020.0Operating Manual2013-06-18/00575607

Pagina 2

1 Introduction101.3.4 DisposalDisposing of the deviceDisposing of the packaging materialThe entire packaging material (cardboard packaging, inserts, p

Pagina 3 - Contents

111 Introduction1.4 Identifying the Device Version1.4.1 NameplatesPositionThe nameplate (B) is affixed to the module case.An additional nameplate with

Pagina 4

1 Introduction12Fabrication no. (F-Nr)Among other things, the fabrication number contains the date of production (year/week).Example: F-Nr = 007003380

Pagina 5

132 Description2.1 Brief descriptionThe analog input module 4-channel is equipped with four universal analog inputs that are elec-trically isolated fr

Pagina 6

2 Description14

Pagina 7

153 Installation3.1 General information on installation/dismountingMounting siteAll modules have protection type IP20 and are only intended for use in

Pagina 8

3 Installation16Minimum distances3.2 Installation/dismounting on DIN railAll modules in the system are intended for installation on a DIN rail accordi

Pagina 9

173 InstallationInstallation, using the example of a multichannel controller module 705010Example installationProcedure:(A) (A1)(A2)Step Activity1 Mou

Pagina 10 - 1 Introduction

3 Installation18Dismounting, using the example of a multichannel controller module 705010Removing the multichannel controller module from the DIN rail

Pagina 11

193 Installation3 Move the modules (B) on the right next to the multichannel controller module that is to be replaced (A) a minimum of 20 mm to the ri

Pagina 13 - 2 Description

3 Installation203.3 Replacing module inserts3.3.1 Input/output modulesReplacement of a module insert, using the example of a multichannel controller m

Pagina 14

213 InstallationRemoving the module insertMounting the module insertCAUTION!Only module inserts of the same type may be used for the replacement.Other

Pagina 15 - 3 Installation

3 Installation223.4 Dimensions22.5103.66.610194.5101.514.5

Pagina 16

234 Electrical connection4.1 Installation notesQualification of personnel• Work on the modules must only be carried out to the extent described and, l

Pagina 17

4 Electrical connection24References to other information• The electromagnetic compatibility meets the standards and regulations cited in the techni-ca

Pagina 18

254 Electrical connection4.3 Connection diagram4.3.1 Display and connection elementsCAUTION!At maximum load, the temperature may exceed 60 °C at the t

Pagina 19

4 Electrical connection264.3.2 Analog inputsConnection Input Terminals Symbol and terminal designationThermocouple 12342 and 36 and 710 and 1114 and 1

Pagina 20

274 Electrical connection4.3.3 Digital inputResistance/potentiometer4-wire circuit12341 to 45 to 89 to 1213 to 161, 5, 9, 132, 6, 10, 143, 7, 11, 154,

Pagina 21

4 Electrical connection284.4 Functional testThe voltage supply must be tested on completion of the electrical connection:StartupThe check described ab

Pagina 22

295 Operation5.1 Display and connection elements(1) Status displays (LED)P = Voltage supplyS = Status1 = Digital input(LED is lit: Active)(2) Analog i

Pagina 23 - 4 Electrical connection

3Contents1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51.1 Available tec

Pagina 24

5 Operation305.2 LED displays"P" LED (Power)The LED is permanently lit in green if the module is being supplied with voltage."S" L

Pagina 25

315 Operation5.2.2 System states and errorsThe following table lists all the system states and errors that are indicated by the "S" LED (Sta

Pagina 26

5 Operation32

Pagina 27

336 Configuration6.1 Digital selectorThe digital selector contains all digital signals that are available in the analog input module 4-channel to conf

Pagina 28

6 Configuration346.2 Analog inputsThe four analog inputs are universal measuring inputs for RTD temperature probes, thermo-couples, resistance transmi

Pagina 29 - 5 Operation

356 ConfigurationLinearization Available options and factory settings depend on the measuring probe selectedLinearPt50 GOST 6651-94Pt100 DIN EN 60751P

Pagina 30

6 Configuration36LinearizationLinearization must be selected according to the sensor (measuring probe).The predefined linearizations can be supplement

Pagina 31

376 ConfigurationMeasuring rangeIn case of customer-specific linearization, these values can not be changed here. They areidentical to the settings ma

Pagina 32

6 Configuration38Resistance Ra or Ro, Rs or Rx, ReThe overall resistance Ra + Rs + Re (or Ro + Rx) must not exceed 4000 Ω.Status after change of confi

Pagina 33 - 6 Configuration

396 Configuration6.2.1 AlarmsLimit value monitoring with one or two alarms and various alarm types can be activated for eachanalog input. In addition,

Pagina 34

Contents44.4 Functional test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 35

6 Configuration40Alarm type and switching differentialEvent textSetup program: Selection of text from a listClick the "..." button to open a

Pagina 36

416 Configuration6.2.2 Fine adjustmentYou can use customer-specific fine adjustment to correct the measured values of the analoginput. In contrast to

Pagina 37

6 Configuration42Performing fine adjustment1) Determine the lower value (as low and constant as possible) with the reference measuring device.Example:

Pagina 38

436 Configuration6.3 Digital inputIn addition to the analog inputs the module provides a digital input.The status of the digital input is indicated by

Pagina 39

6 Configuration44Signal suppressionWhen signal suppression is active, the input signal and the inverting and delay parameters areirrelevant. In this c

Pagina 40

456 Configuration6.4 NV connecting listThe NV connecting list is used to link external inputs (NV_...) of the analog input module 4-channel to signals

Pagina 41

6 Configuration46Replacement valueThe replacement value is used if the relevant signal is not available (connection to base unitinterrupted or system

Pagina 42

476 Configuration6.4.1 Digital signals (overview)The following table contains all signals that are available in the NV connecting list for connec-tion

Pagina 43

6 Configuration48Alarm analog variablesAlarm1 ExAI1 to Alarm1 ExAI64 Alarm signal 1 of analog variable 1 to 64Alarm2 ExAI1 to Alarm2ExAI64 Alarm signa

Pagina 44

496 ConfigurationAlarms/FaultsCAlarm/Fault System collective alarm or system fault (cen-tral processing unit and modules)CAlarm/Fault ackn. System col

Pagina 45

51 Introduction1.1 Available technical documentationThe documents specified below are available for the measuring, control, and automation sys-tem.1.1

Pagina 46

6 Configuration50Multichannel controller moduleController C01ManualMode to C04ManualModeManual mode active for controller channel 1to4C01TuneActive to

Pagina 47

516 ConfigurationAnalog input module 4-channelAnalog inputs AI01Alarm1 to AI04Alarm1 Alarm signal 1 of analog input 1 to 4AI01Alarm2 to AI04Alarm2 Ala

Pagina 48

6 Configuration526.4.2 Replacement values (overview)The following table contains the replacement values with their factory settings. Replacementvalues

Pagina 49

537 Configuration – in setup program only7.1 Customer-specific linearizationYou can use the customer-specific linearization to create a customized lin

Pagina 50

7 Configuration – in setup program only54Measured valueThe table below shows the admissable measured value range of the analog inputs, dependingon the

Pagina 51

557 Configuration – in setup program only7.1.1 Grid pointsCustomer-specific linearization is specified by entering up to 45 grid points (pairs of valu

Pagina 52

7 Configuration – in setup program only56Displaying linearization on a graphic ("Display graphic" button)Use this button to create a graphic

Pagina 53 - <<<<

577 Configuration – in setup program only7.1.2 FormulaCustomer-specific linearization is specified using a 4th order polynomial. The polynomial is cal

Pagina 54 - limited as follows:

7 Configuration – in setup program only58Displaying linearization on a graphic ("Display graphic" button)Use this button to create a graphic

Pagina 55 - 7.1.1 Grid points

598 Online parameters8.1 Calibrate / test8.1.1 Analog inputSetup dialogParameterTIP!An active connection between the setup program and the central pro

Pagina 56

1 Introduction61.1.4 Special modules1.1.5 Operating, visualization, recording1.1.6 Power supply unitsProduct Type of documentation No. Printed PDF fil

Pagina 57 - 7.1.2 Formula

8 Online parameters60TestThe results of the test measurement are shown in the display field.8.1.2 Digital inputSetup dialogParameterParameter Selectio

Pagina 58

618 Online parameters8.1.3 Internal Pt100Setup dialogThis dialog displays the cold junction temperatures of analog inputs 1 to 4 ("Channel 1"

Pagina 59 - 8 Online parameters

8 Online parameters628.1.4 LED testSetup dialogParameterParameter Selection/settings DescriptionS LED To test the LED, click the required status to se

Pagina 60

638 Online parameters8.1.5 Calibration constantsSetup dialogThis dialog displays the calibration constants of the analog inputs.

Pagina 61

8 Online parameters648.1.6 VersionsSetup dialogThis dialog displays the module versions.

Pagina 62

659 Appendix9.1 Technical data9.1.1 Analog inputsGeneral informationThermocouplesNumber 4A/D converter Dynamic resolution up to 16 bitDesignation Stan

Pagina 63

9 Appendix66RTD temperature probeDesignation Standard Measuring range Measuring accu-racy1Ambienttemperature influ-encePt100 DIN EN 60751 -200 to +850

Pagina 64

679 AppendixStandard signalsMeasuring circuit monitoringIn the event of an error the digitized output values move to a defined status.9.1.2 Digital in

Pagina 65 - 9 Appendix

9 Appendix689.1.3 Electrical data9.1.4 Case and ambient conditions9.1.5 Approval/approval marksVoltage supplyConnection Lateral (feed via base unit or

Pagina 67

71 Introduction1.2 Safety information1.2.1 Warning symbols1.2.2 Note signsDANGER!This symbol indicates that injury to persons caused by electrical sho

Pagina 68

JUMO GmbH & Co. KGStreet address:Moritz-Juchheim-Straße 136039 Fulda, GermanyDelivery address:Mackenrodtstraße 1436039 Fulda, GermanyPostal addres

Pagina 69

1 Introduction81.2.3 Intended useThe modules described are intended for measuring, control, and automation tasks in an indus-trial environment, as des

Pagina 70

91 Introduction1.3 Acceptance of goods, storage, and transport1.3.1 Checking the delivery• Ensure that the packaging and contents are not damaged • Ch